Table 7 Results for 69 bus system with DG at upf

From: Optimal DG placement for benefit maximization in distribution networks by using Dragonfly algorithm

  Without DG Voltage sensitivity index method (Murthy and Kumar 2013) Proposed method
DG location   65 61
DG size (kW)   1450 1872.7
TLP (kW) 225 112.0217 83.22
TLR (kVAR) 102.1091 55.1172 40.57
Vmin (p.u.) 0.909253 0.9660621 0.9685
Cost of energy losses ($) 18,101.7621 9017.2139 6694
Cost of Pdg ($/MW h) 29.25 37.7