Skip to main content

Table 7 Results for 69 bus system with DG at upf

From: Optimal DG placement for benefit maximization in distribution networks by using Dragonfly algorithm

 

Without DG

Voltage sensitivity index method (Murthy and Kumar 2013)

Proposed method

DG location

 

65

61

DG size (kW)

 

1450

1872.7

TLP (kW)

225

112.0217

83.22

TLR (kVAR)

102.1091

55.1172

40.57

Vmin (p.u.)

0.909253

0.9660621

0.9685

Cost of energy losses ($)

18,101.7621

9017.2139

6694

Cost of Pdg ($/MW h)

–

29.25

37.7