Skip to main content

Table 14 Table of outcome frequencies (per year) by site

From: Large-scale energy storage system: safety and risk assessment

Outcomes

Safety barriers

  

Damage Levels

 

Frequency (per year)

      
 

FD

F1

F2

Fire hazard

BESS damage

A1

A2

B1

B2

B3

B4

B5

1.1

1

1

x

1

1

1.845E–04

3.399E–04

8.082E–04

1.200E–03

1.593E–03

1.985E–03

2.181E–03

1.2

1

2

1

2

1

8.188E–06

1.509E–05

3.587E–05

5.328E–05

7.070E–05

8.811E–05

9.682E–05

1.3

1

2

0

2

2

9.098E–07

1.676E–06

3.986E–06

5.920E–06

7.855E–06

9.790E–06

1.076E–05

1.4

1

0

1

3

2

1.936E–05

3.566E–05

8.480E–05

1.260E–04

1.671E–04

2.083E–04

2.289E–04

1.5

1

0

0

3

3

2.151E–06

3.963E–06

9.423E–06

1.400E–05

1.857E–05

2.314E–05

2.543E–05

1.6

0

X

1

3

2

1.955E–06

3.602E–06

8.566E–06

1.272E–05

1.688E–05

2.104E–05

2.312E–05

1.7

0

X

0

3

3

2.173E–07

4.003E–07

9.518E–07

1.414E–06

1.876E–06

2.338E–06

2.569E–06