Table 8 Probability of failure on demand of safety systems (Gully, 2019)

From: Large-scale energy storage system: safety and risk assessment

Barriers

Code

Hazard Type

Barrier Type

PFD

Function

BMS monitoring

BMS

Electrical, thermal

Active

0.10

Currrent, voltage, SoC, temperature monitoring

Cooling system

T1

Thermal

Active

0.10

Temperature regulation of BESS

Space

Thermal Insulation

T2

Thermal

Passive

0.10

Minimize heat transfer between battery modules/racks

Fire and smoke detector

FD

Fire

Detection

0.01

Detect smoke and produce visual and audible alert at control centre

Active fire suppression

F1

Fire

Active

0.10

Fire suppression, extinguishment, and cooling

Emergency fire response

F2

Fire

Emergency

0.10

Firefighter action plan

Gas detection

XD

Explosion

Detection

0.01

Early detection for accumulation of flammable gases before reaching explosive

Emergency ventilation

X1

Explosion

Active

0.10

Removal of gas before reaching explosive concentration

Emergency shutdown

E1

Electrical/Fire

Active

0.01

Electrical isolation

Circuit breaker

E2

Electrical

Active

0.10

Electrical isolation